Use this wire size calculator to estimate an electrical conductor size from load current, circuit voltage, conductor material, and run length while also checking voltage drop.
About this calculator
Use this wire size calculator to estimate an electrical conductor size from load current, circuit voltage, conductor material, and run length while also checking voltage drop. It is especially useful when amperage alone would suggest one conductor size but a long run requires upsizing. The correct wire size is not chosen from amps alone: continuous-load rules, conductor material, insulation rating, terminal temperature limits, ambient temperature, current-carrying conductor count, installation method, equipment instructions, and locally adopted electrical-code requirements can all change the final answer. Use the result for preliminary planning and verification, then confirm the exact installation requirements before construction.
Electrical wire sizing normally requires two checks. First, the ampacity check determines whether the conductor can carry the calculated load after required adjustment and correction factors. Second, the voltage-drop check estimates whether conductor resistance over the circuit length will reduce voltage excessively at the load. The larger conductor required by either check generally controls. This makes the calculator useful as a wire size calculator for amps and distance, a wire size calculator with voltage drop, and an AWG sizing reference. American Wire Gauge works in reverse: a smaller AWG number represents a larger conductor. Copper and aluminum also differ in resistance, ampacity, termination, and installation requirements.
Treat the reported gauge as a starting point that must be checked against the exact installation. A result of 8 AWG does not mean every 8 AWG conductor is acceptable: insulation type, conductor material, wet-location rating, raceway conditions, terminal ratings, and equipment listings still matter. Long runs may need larger wire even when minimum ampacity is adequate. Special loads such as motors, HVAC equipment, EV charging equipment, services, and grounding conductors can have application-specific rules that a general wire-size calculator does not replace.
Worked examples
Wire size calculator with voltage drop
A 240 V load draws 24 A and is located a substantial distance from the panel.
- Determine whether the load is continuous and apply the required load calculation
- Check minimum conductor ampacity using the applicable conductor and terminal ratings
- Enter the one-way circuit distance for the voltage-drop calculation
- Compare the ampacity-based gauge with the voltage-drop-based gauge
Result: The final design uses whichever requirement produces the larger conductor, followed by a code and equipment-instruction review.
Wire size from amps and distance
A circuit has acceptable ampacity on a short run, but the equipment is moved much farther from the source.
- Keep the calculated load current unchanged
- Increase the one-way circuit distance to the actual field value
- Recalculate voltage drop
- Upsize the conductor if the longer run causes excessive drop
Result: A longer circuit can require a larger AWG conductor even when the connected load current has not changed.
Copper versus aluminum feeder planning
A feeder is being evaluated with either copper or aluminum conductors.
- Select the intended conductor material in the calculator
- Compare the required gauge and estimated voltage drop
- Confirm that all lugs and equipment are listed for the selected material
- Account for raceway size, bending space, termination preparation, and local requirements
Result: Aluminum commonly requires a larger conductor size than copper for the same load, but the complete installation—not gauge alone—determines suitability.