Voltage Drop Calculator

Use this voltage drop calculator to estimate how much voltage is lost as current travels through a copper conductor.

Voltage Drop Calculator Tool

Enter your values in the calculator above, then use the explanations below to understand the result, check assumptions, and compare scenarios.

About this calculator

Use this voltage drop calculator to estimate how much voltage is lost as current travels through a copper conductor. It supports 12 V, 24 V, 120 V, 208 V, 240 V, 277 V, and 480 V source selections and is useful for long branch circuits, feeders, battery-powered equipment, outdoor loads, landscape lighting, and other runs where conductor resistance can reduce delivered voltage. Enter source voltage, load current, one-way distance, and AWG size to estimate voltage drop and percentage drop.

Voltage drop depends mainly on current, conductor resistance, and circuit length. Resistance increases as conductors get longer and decreases as conductors get larger. This calculator uses copper-wire resistance values and a simple two-wire round-trip model. It is well suited to common DC and single-phase two-wire checks, but it is not a three-phase impedance calculator and does not model aluminum conductors or reactive AC impedance.

The calculated percentage drop is a design indicator, not a universal pass/fail code determination. A 3% branch-circuit target and 5% combined feeder-plus-branch target are commonly used design guidelines, but the controlling requirement can depend on the adopted electrical code, equipment instructions, project specifications, and local amendments. If the calculated drop is too high, possible remedies include increasing conductor size, shortening the run, reducing current, increasing system voltage where appropriate, or moving equipment closer to the source.

Worked examples

12V DC voltage drop on a long wire run

A 12 V load is located far from a battery or DC power source.

  1. Select 12 V as the source voltage
  2. Enter the actual load current
  3. Enter the one-way wire distance
  4. Select the copper AWG size and review voltage drop and percentage drop

Result: Because the source voltage is low, even a small absolute voltage loss can become a significant percentage drop.

24V low-voltage circuit check

A 24 V control or lighting circuit has a long cable run.

  1. Select 24 V
  2. Enter operating current and one-way distance
  3. Choose the copper wire gauge
  4. Compare delivered voltage with the equipment requirement

Result: The calculation helps determine whether a larger conductor may improve voltage at the load.

Wire voltage drop on a long 240 V run

A 240 V load draws 30 A at a long distance from the panel.

  1. Select 240 V
  2. Enter 30 A load current
  3. Enter one-way distance and copper AWG size
  4. Compare the calculated percentage drop with the project design target

Result: If the percentage drop is excessive, a larger conductor may be needed even when the original conductor has enough ampacity.

Landscape lighting voltage drop check

A long low-voltage lighting run shows dimmer fixtures near the end of the circuit.

  1. Use the supported source voltage closest to the system voltage
  2. Enter actual operating current and one-way distance
  3. Select copper conductor size
  4. Review delivered voltage before changing conductor size or circuit layout

Result: Low-voltage systems can be especially sensitive to conductor losses, so modest voltage loss may noticeably affect performance.

Practical tips

  • Enter one-way distance; the calculator accounts for the outgoing and return conductor path.
  • Use actual operating load current rather than breaker rating when estimating normal voltage drop.
  • The calculator uses copper-wire resistance values; do not use the result as an aluminum-conductor calculation.
  • Check voltage drop separately from ampacity, conductor adjustment factors, and overcurrent protection.
  • For 12 V and 24 V circuits, watch percentage drop closely because low source voltage makes the same voltage loss more significant.
  • Use a dedicated three-phase voltage-drop method when phase relationships and AC impedance matter.

Common mistakes

  • Entering round-trip distance when the calculator expects one-way distance.
  • Assuming the calculator models aluminum conductors when its resistance table is based on copper wire.
  • Using breaker amperage instead of actual load current for the operating-voltage estimate.
  • Treating a common voltage-drop design target as a mandatory rule for every jurisdiction and application.
  • Using this simple two-wire model for a three-phase or complex AC impedance calculation.
  • Checking voltage drop but failing to verify conductor ampacity and equipment requirements separately.

Key terms

Voltage drop
The reduction in voltage caused by current flowing through conductor resistance or impedance.
One-way distance
The physical distance from source to load before the return path is accounted for by the calculator.
Resistance
Opposition to current flow in a conductor or component, measured in ohms.
Percentage voltage drop
Voltage drop divided by source voltage, expressed as a percentage.
AWG
American Wire Gauge, a sizing system in which lower gauge numbers generally indicate larger conductors.

Frequently asked questions

Can I use this as a 12V voltage drop calculator?
Yes. Select 12 V, enter load current, one-way distance, and copper AWG size. The result shows both voltage loss and percentage drop, which is especially useful for low-voltage DC circuits.
Can I calculate 24V DC voltage drop?
Yes. Select 24 V and enter the operating current, one-way distance, and copper wire gauge. Verify the delivered voltage against the connected equipment's requirements.
How do I calculate voltage drop from resistance?
For a simple resistive path, voltage drop is current multiplied by circuit resistance. This calculator derives resistance from copper AWG size and circuit length, then applies the load current.
Is voltage drop the same as wire ampacity?
No. Ampacity addresses conductor heating under specified conditions. Voltage drop addresses how much source voltage is lost along the circuit. Both checks can affect final conductor size.
What voltage drop percentage is acceptable?
A 3% branch-circuit target and 5% combined feeder-plus-branch target are common design guidelines, but the governing requirement depends on applicable code, equipment instructions, and project specifications.
Can I use this for three-phase voltage drop?
No. This calculator uses a simple two-wire round-trip resistance model. Three-phase systems should use a method that accounts for the correct three-phase formula and, where needed, AC impedance and power factor.