Use this transformer calculator to estimate the ideal primary-to-secondary voltage ratio and full-load current from primary voltage, secondary voltage, and transformer VA rating.
About this calculator
Use this transformer calculator to estimate the ideal primary-to-secondary voltage ratio and full-load current from primary voltage, secondary voltage, and transformer VA rating. It is useful for preliminary checks of step-down and step-up transformers, control transformers, low-voltage supplies, and other AC transformer applications. The calculator reports the ideal turns/voltage ratio and approximate primary and secondary current at rated apparent power.
For an ideal transformer, the voltage ratio equals primary voltage divided by secondary voltage, and full-load current is estimated from apparent power divided by winding voltage. If a transformer is rated 5,000 VA at 240 V primary and 120 V secondary, the ideal ratio is 2:1, primary current is about 20.8 A, and secondary current is about 41.7 A. Real transformers also have losses, regulation, inrush, temperature rise, and installation constraints that are not represented by the ideal relationship.
Use the result to understand voltage ratio and nominal full-load current, not to finalize transformer selection or overcurrent protection. Final design should verify standard kVA/VA ratings, primary and secondary conductor ampacity, overcurrent protection, grounding/bonding, inrush, temperature class, enclosure, frequency, impedance, efficiency, harmonic loading, and manufacturer instructions. Three-phase transformer sizing also requires the correct three-phase kVA/current relationship rather than the simple single-phase VA ÷ V formula.