Calculate three-phase kW from volts and amps
A balanced 480 V three-phase load draws 40 amps at 0.85 power factor.
- Use kW = √3 × V × I × PF ÷ 1000
- Multiply 1.732 × 480 × 40 × 0.85
- Divide by 1000
Result: The load is about 28.3 kW.
Use this three-phase power calculator to estimate watts, kilowatts, apparent power, current, voltage, or power factor for balanced three-phase systems.
Enter your values in the calculator above, then use the explanations below to understand the result, check assumptions, and compare scenarios.
Use this three-phase power calculator to estimate watts, kilowatts, apparent power, current, voltage, or power factor for balanced three-phase systems. It is useful for motors, commercial HVAC, pumps, machine tools, generators, and industrial distribution. Three-phase calculations differ from single-phase calculations because line-to-line voltage and the square-root-of-three factor are part of the relationship. Use the result for planning and comparison, then verify nameplate data, conductor sizing, overcurrent protection, and application-specific electrical requirements.
For a balanced three-phase load, apparent power is based on √3 × line voltage × line current. Real power also includes power factor, so kW = √3 × V × I × PF ÷ 1000. Rearranging the formula lets the calculator solve for current, voltage, or power from the other known values. This page owns three-phase power conversion intent; the Watts to Amps and Amps to Watts calculators are better suited to simple DC and single-phase conversions.
The result estimates steady-state electrical relationships for a balanced load. It does not model unbalanced phases, harmonics, motor starting, transformer impedance, voltage drop, or equipment-specific protection rules. For motors, HVAC, generators, and service or feeder work, use nameplate and design data where available rather than relying on a generic kW-to-amps result alone.
A balanced 480 V three-phase load draws 40 amps at 0.85 power factor.
Result: The load is about 28.3 kW.
A 30 kW balanced load operates at 208 V three-phase with 0.9 power factor.
Result: The estimated current is about 92.5 amps.
The same balanced 30 kW load at 0.9 power factor is compared at 208 V and 480 V.
Result: The higher-voltage system requires substantially less line current for the same real power.