InfiniteCalcs

Three Phase Power Calculator

Use this three-phase power calculator to estimate watts, kilowatts, apparent power, current, voltage, or power factor for balanced three-phase systems.

Three Phase Power Calculator Tool

Enter your values in the calculator above, then use the explanations below to understand the result, check assumptions, and compare scenarios.

About this calculator

Use this three-phase power calculator to estimate watts, kilowatts, apparent power, current, voltage, or power factor for balanced three-phase systems. It is useful for motors, commercial HVAC, pumps, machine tools, generators, and industrial distribution. Three-phase calculations differ from single-phase calculations because line-to-line voltage and the square-root-of-three factor are part of the relationship. Use the result for planning and comparison, then verify nameplate data, conductor sizing, overcurrent protection, and application-specific electrical requirements.

For a balanced three-phase load, apparent power is based on √3 × line voltage × line current. Real power also includes power factor, so kW = √3 × V × I × PF ÷ 1000. Rearranging the formula lets the calculator solve for current, voltage, or power from the other known values. This page owns three-phase power conversion intent; the Watts to Amps and Amps to Watts calculators are better suited to simple DC and single-phase conversions.

The result estimates steady-state electrical relationships for a balanced load. It does not model unbalanced phases, harmonics, motor starting, transformer impedance, voltage drop, or equipment-specific protection rules. For motors, HVAC, generators, and service or feeder work, use nameplate and design data where available rather than relying on a generic kW-to-amps result alone.

Worked examples

Calculate three-phase kW from volts and amps

A balanced 480 V three-phase load draws 40 amps at 0.85 power factor.

  1. Use kW = √3 × V × I × PF ÷ 1000
  2. Multiply 1.732 × 480 × 40 × 0.85
  3. Divide by 1000

Result: The load is about 28.3 kW.

Calculate amps from three-phase kW

A 30 kW balanced load operates at 208 V three-phase with 0.9 power factor.

  1. Rearrange to I = kW × 1000 ÷ (√3 × V × PF)
  2. Use 208 V line-to-line
  3. Include the 0.9 power factor

Result: The estimated current is about 92.5 amps.

Compare 208 V and 480 V current

The same balanced 30 kW load at 0.9 power factor is compared at 208 V and 480 V.

  1. Calculate current at 208 V
  2. Calculate current again at 480 V
  3. Compare the two current values at the same kW and power factor

Result: The higher-voltage system requires substantially less line current for the same real power.

Practical tips

  • Use line-to-line voltage for standard balanced three-phase power formulas.
  • Include power factor for motors and other non-resistive AC loads.
  • Use nameplate current for motors and HVAC equipment when required.
  • Check phase balance when adding large three-phase loads to an existing panel.
  • Account for starting current and voltage drop separately from steady-state power calculations.

Common mistakes

  • Forgetting the √3 factor in balanced three-phase calculations.
  • Using line-to-neutral voltage when the formula expects line-to-line voltage.
  • Ignoring power factor on inductive loads.
  • Using a single-phase watts-to-amps formula on a three-phase load.
  • Sizing conductors or protection directly from calculated kW instead of required equipment data.

Key terms

Line-to-line voltage
Voltage measured between two phase conductors in a polyphase system.
Power factor
The ratio of real power to apparent power in an AC circuit.
Balanced load
A three-phase load with approximately equal current on each phase.
Apparent power
Voltage-current product in an AC circuit, measured in VA or kVA.

Frequently asked questions

What is the three-phase power formula?
For a balanced three-phase load, real power in watts equals √3 multiplied by line voltage, line current, and power factor.
How do I calculate amps from three-phase kW?
Multiply kW by 1000, then divide by √3 times line-to-line voltage times power factor. Use nameplate current for final equipment design when available.
Why is √3 used in three-phase calculations?
The √3 factor comes from the 120-degree phase relationship between the three phases and the relationship between line and phase quantities in a balanced system.
Should I use line-to-line or line-to-neutral voltage?
Standard three-phase power formulas using √3 normally use line-to-line voltage. Use the voltage specified by the calculator and equipment data.
Can this calculator size a three-phase motor circuit?
Not by itself. Motor circuits also require nameplate data, starting-current review, conductor sizing, overload protection, short-circuit protection, and applicable electrical requirements.