Use this power factor correction calculator to estimate the capacitor-bank kVAR needed to improve an AC load from its current power factor to a target power factor.
About this calculator
Use this power factor correction calculator to estimate the capacitor-bank kVAR needed to improve an AC load from its current power factor to a target power factor. It supports both single-phase and three-phase systems and reports reactive power before and after correction, apparent power, current reduction, and an estimated capacitance value. The result is useful for preliminary planning of industrial and commercial loads, motors, and facility systems, but final capacitor-bank design must consider switching strategy, harmonics, resonance risk, equipment ratings, and the utility tariff.
The required correction is based on Qc = P × [tan(arccos(PF1)) − tan(arccos(PF2))], where P is real power in kW, PF1 is the existing power factor, and PF2 is the target. The calculator also estimates kVA before and after correction and the reduction in line current. Frequency and voltage affect the corresponding capacitance in microfarads, so 50 Hz and 60 Hz systems should not be treated as interchangeable.
A calculated kVAR value is a preliminary compensation target, not an automatic equipment selection. Fixed capacitor banks can work for stable loads, while variable loads may require stepped or automatic correction. Avoid correcting blindly to unity power factor; over-correction can create leading power factor and contribute to voltage or resonance problems. For installations with significant harmonics, capacitor banks may require detuning reactors or a more complete power-quality study.