Power factor from kW and kVA
A facility load uses 80 kW while drawing 100 kVA.
- Use PF = kW ÷ kVA
- Divide 80 by 100
- PF = 0.80
Result: The load has a power factor of 0.80.
Use this power factor calculator to relate real power in kW, apparent power in kVA, reactive power in kVAR, and phase angle for AC loads.
Enter your values in the calculator above, then use the explanations below to understand the result, check assumptions, and compare scenarios.
Use this power factor calculator to relate real power in kW, apparent power in kVA, reactive power in kVAR, and phase angle for AC loads. It supports common electrical-analysis tasks such as calculating PF from kW and kVA, estimating reactive power, and understanding the power triangle. The results are useful for motors, transformers, commercial equipment, and facility-load analysis, but final correction or equipment decisions should use measured data and project-specific requirements.
Power factor is the ratio of real power to apparent power: PF = kW ÷ kVA. A value closer to 1 means a larger share of the apparent power is doing real work. For a sinusoidal relationship, phase angle can be estimated from θ = cos⁻¹(PF), and reactive power from Q = √(S² − P²). Lower power factor generally increases current for the same real power, which can increase conductor, transformer, and system loading.
Use the calculator to evaluate the electrical relationship among kW, kVA, kVAR, and phase angle. A low PF result does not automatically mean a capacitor bank should be installed. Utility tariffs, harmonics, load variation, motor operating condition, switching strategy, resonance risk, and equipment ratings all matter. Single-phase and three-phase systems can both have power factor, but voltage-current calculations must match the circuit configuration.
A facility load uses 80 kW while drawing 100 kVA.
Result: The load has a power factor of 0.80.
A load uses 50 kW at a power factor of 0.90.
Result: The estimated reactive power is about 24.2 kVAR.
A balanced three-phase load has known real power and apparent power values.
Result: Power factor itself remains kW ÷ kVA, while the method used to determine kVA depends on the circuit configuration.
| Power factor | Apparent power | Approx. reactive power |
|---|---|---|
| 1.00 | 100.0 kVA | 0.0 kVAR |
| 0.95 | 105.3 kVA | 32.9 kVAR |
| 0.90 | 111.1 kVA | 48.4 kVAR |
| 0.80 | 125.0 kVA | 75.0 kVAR |