Torque-based motor sizing
A machine requires 20 lb-ft of shaft torque at 1,750 RPM.
- Use HP = torque × RPM ÷ 5252
- Multiply 20 by 1,750
- Divide by 5,252
Result: Required shaft power is about 6.66 HP before efficiency and design margin are considered.
Use this motor sizing calculator to estimate required motor horsepower or kilowatts from mechanical torque, rotational speed, efficiency, and an appropriate ser
Enter your values in the calculator above, then use the explanations below to understand the result, check assumptions, and compare scenarios.
Use this motor sizing calculator to estimate required motor horsepower or kilowatts from mechanical torque, rotational speed, efficiency, and an appropriate service factor or design margin. It supports preliminary electric motor sizing for rotating machinery such as pumps, fans, conveyors, mixers, and driven equipment. Final motor selection should also account for starting torque, acceleration, duty cycle, enclosure, ambient conditions, controls, and the driven machine's load profile.
Rotating mechanical power is determined by torque and speed. In U.S. customary units, horsepower can be estimated from torque in lb-ft and rotational speed in RPM using HP = torque × RPM ÷ 5252. Metric calculations use the equivalent torque-speed power relationship to determine watts or kilowatts. If the required mechanical output is known, motor input and selection also depend on efficiency and the design margin needed for the application.
Select the next appropriate standard motor rating above the calculated requirement after considering the actual load profile. A motor that meets steady-state horsepower may still be unsuitable if the application has high breakaway torque, frequent starts, rapid acceleration, cyclic loading, high ambient temperature, altitude, or a demanding duty cycle. Variable-frequency-drive applications also require motor and drive compatibility checks, particularly at low speed and for insulation, cooling, and overload performance.
A machine requires 20 lb-ft of shaft torque at 1,750 RPM.
Result: Required shaft power is about 6.66 HP before efficiency and design margin are considered.
A calculation produces a required motor output above a common standard rating.
Result: Do not round down when doing so would leave the motor below the required continuous mechanical load.
A conveyor has higher torque during startup than during normal running.
Result: Steady-state horsepower alone is not enough to validate a high-starting-torque application.
| Torque | Speed | Approx. shaft power |
|---|---|---|
| 10 lb-ft | 1,750 RPM | 3.33 HP |
| 20 lb-ft | 1,750 RPM | 6.66 HP |
| 30 lb-ft | 1,750 RPM | 10.0 HP |
| 20 lb-ft | 3,500 RPM | 13.33 HP |