5 kW to amps at 240 V single phase
A 5 kW resistive load operates at 240 V single phase with PF = 1.0.
- Convert 5 kW to 5,000 W
- Use I = P ÷ (V × PF)
- Divide 5,000 by 240
Result: The estimated current is about 20.83 A.
Use this kilowatts to amps calculator to convert real electrical power in kW into estimated current for single-phase or balanced three-phase AC circuits.
Enter your values in the calculator above, then use the explanations below to understand the result, check assumptions, and compare scenarios.
Use this kilowatts to amps calculator to convert real electrical power in kW into estimated current for single-phase or balanced three-phase AC circuits. Enter kilowatts, voltage, phase, and power factor to calculate amps for equipment, motors, generators, HVAC loads, and preliminary electrical planning. The result is an operating-current estimate and does not replace equipment nameplate data or code-based conductor and overcurrent-protection calculations.
One kilowatt equals 1,000 watts. For single-phase AC, current is estimated with I = (kW × 1,000) ÷ (V × PF). For balanced three-phase AC, use I = (kW × 1,000) ÷ (√3 × V × PF). This is why the same kW load can draw very different amperage at 120 V, 240 V, 208 V three-phase, or 480 V three-phase. Lower power factor also increases current for the same real power and voltage.
Use the calculated amps to understand the relationship among kW, voltage, phase, and power factor. Do not automatically use the result as breaker size, wire ampacity, transformer size, or service demand. Motors and listed equipment may have nameplate current, minimum circuit ampacity, maximum overcurrent protection, efficiency, starting-current, and duty requirements that govern the final design.
A 5 kW resistive load operates at 240 V single phase with PF = 1.0.
Result: The estimated current is about 20.83 A.
A 10 kW load operates at 240 V with a power factor of 1.0.
Result: The estimated current is about 41.67 A.
A balanced 15 kW load operates at 480 V three phase with PF = 0.90.
Result: The estimated line current is about 20.0 A.
| Power | 120 V 1-phase | 240 V 1-phase |
|---|---|---|
| 1 kW | 8.33 A | 4.17 A |
| 5 kW | 41.67 A | 20.83 A |
| 10 kW | 83.33 A | 41.67 A |
| 20 kW | 166.67 A | 83.33 A |