Generator Size Calculator

Use this generator size calculator to estimate the generator capacity needed from total running watts, the largest starting surge, power factor, and a safety margin.

Generator Size Calculator Tool

Enter your values in the calculator above, then use the explanations below to understand the result, check assumptions, and compare scenarios.

About this calculator

Use this generator size calculator to estimate the generator capacity needed from total running watts, the largest starting surge, power factor, and a safety margin. It is useful for homes, portable-generator planning, jobsites, events, pumps, refrigerators, air conditioners, and mixed motor loads. The calculator reports required kW and kVA and recommends the next standard generator size that meets the calculated demand.

Generator sizing must account for both continuous running load and motor-starting surge. The calculator estimates peak demand as total running watts plus the extra starting surge of the largest motor load, then applies a selected safety margin. It converts the result to kW and kVA using power factor. This is more useful than simply adding appliance nameplate watts because motors and compressors can require significantly more power during startup.

Treat the result as a planning estimate. Actual generator selection should verify manufacturer ratings, altitude and temperature derating, fuel type, voltage configuration, transfer equipment, neutral/grounding arrangement, motor-starting performance, harmonic sensitivity, and local code. Whole-house standby systems and large motor loads may require a more detailed load study than a simple wattage total.

Worked examples

Generator size for home essentials

A home needs 4,500 W of running load, and the largest motor starts at 3,000 W while running at 1,000 W.

  1. Starting surge allowance = 3,000 − 1,000 = 2,000 W
  2. Peak demand = 4,500 + 2,000 = 6,500 W
  3. Apply the selected safety margin
  4. Convert required kW to kVA using the entered power factor

Result: The calculator recommends the next standard generator size above the adjusted peak demand.

Generator size for a jobsite with motor loads

Several tools run together, but the compressor has the largest startup requirement.

  1. Add the running watts of all simultaneous tools
  2. Enter the compressor starting watts and its running watts
  3. Use an appropriate power factor and safety margin
  4. Review the recommended kW and kVA

Result: The estimate includes one dominant starting surge instead of stacking every motor's startup current at the same instant.

Practical tips

  • Use actual running and starting watts from equipment data whenever available.
  • Separate the largest motor's starting watts from its running watts to avoid double-counting.
  • Use kVA as well as kW when the load contains motors or other reactive equipment.
  • Leave practical headroom instead of operating continuously at the calculated minimum.
  • For whole-house standby systems, verify load-management strategy and transfer-switch requirements.

Common mistakes

  • Adding every motor starting surge together even though startup can be sequenced.
  • Ignoring starting watts for air conditioners, pumps, refrigerators, and compressors.
  • Using kW and kVA as though they are identical when power factor is below 1.0.
  • Sizing only from breaker ratings instead of actual connected and starting loads.
  • Ignoring altitude, temperature, fuel, or manufacturer derating.

Key terms

Running watts
The continuous real-power demand while equipment is operating normally.
Starting watts
Short-duration power required when a motor or compressor starts.
kVA
Kilovolt-amperes, the unit of apparent power often used for generator ratings.
Safety margin
Additional generator capacity above calculated peak demand to provide operating headroom.

Frequently asked questions

What size generator do I need for a house?
Add the running watts of the loads you want to operate simultaneously, include the largest starting surge, and add a reasonable safety margin. Whole-house systems with central air conditioning or electric heating often require much more capacity than an essentials-only backup system.
How do I calculate generator size from watts?
Start with total running watts, add the extra starting surge of the largest motor load, then apply a safety margin. Divide watts by 1,000 for kW and account for power factor when converting to kVA.
Why are starting watts important?
Motors and compressors can draw several times their normal running power during startup. A generator that can handle the running load may still trip or sag if it cannot supply the startup surge.
What is the difference between generator kW and kVA?
kW is real power and kVA is apparent power. They are related by power factor: kW = kVA × PF. Motor-heavy loads can require more kVA than their real-power kW value suggests.
Can I use this for a whole-house generator?
Yes for preliminary sizing, but final whole-house selection should verify actual appliance loads, HVAC starting requirements, load shedding, fuel supply, transfer equipment, and the generator manufacturer's sizing guidance.
Can I size a generator from amps?
Convert the relevant current and voltage to power using the correct single-phase or three-phase relationship, then include starting and safety-margin requirements before selecting a generator.